Switchgear From stock · used switchgear

ABB SafeRing CCF, 24 kV

SF₆-insulated three-panel ring main unit built in 2019: two cable switches and one switch-fuse panel for transformer protection. Dismantled in working order and available from stock.

Front: two cable panels (C) and the switch-fuse panel (F)
Main nameplate: SafeRing type C C F, 24 kV, 2019
Cable panel with SF₆ pressure gauge, fault indicator and voltage detection
Main nameplate

Rated values

Type ABB SafeRing CCF · Ring main unit (RMU)
Year of manufacture 2019
Serial number 201912554830005
Rated voltage (Ur) 24 kV
Rated frequency (fr) 50 Hz
Lightning impulse withstand voltage (Up) 125 kV
Power-frequency withstand voltage (Ud) 50 kV
Rated current, busbar (Ir) 630 A
Short-time withstand current, busbar (Ik, tk) 16 kA / 3 s
Peak withstand current (Ip) 40 kA
Internal arc classification IAC AFL 20 kA, 1 s
Insulating gas SF₆ · 3,1 kg
Rated filling pressure, relative (Pre) 0,04 MPa
Ambient temperature, indoor −25 °C … +40 °C
Mass 450 kg
Standard IEC 62271-200
Standard dimensions, W × D × H 1021 mm × 765 mm × 1336 mm

Standard dimensions from the ABB catalogue, not measured on this unit.

Panel configuration

C – C – F: two cable panels and one fuse panel

Values as printed on the nameplate of each panel. The maximum fuse-link rating comes from the ABB catalogue.

2 × Cable switch

Switch-disconnector for the ring cable, with earthing switch.

Class
E3, M1
Rated and load-breaking current (Ir, I1, I2a)
630 A
Cable-charging breaking current (I4c)
135 A
Short-time withstand current (Ik, tk)
16 kA / 3 s
Short-circuit making current (Ima)
40 kA
Load-breaking operations (n)
100
Earthing switch
E2 · 16 kA / 3 s
Standards
IEC 60265-1 · IEC 62271-102
Fitted equipment
  • Horstmann SIGMA F+E · short-circuit and earth-fault indicator
  • Horstmann WEGA 1.2 C · capacitive voltage detection, IEC 61243-5

Switch-fuse combination

Switch-disconnector with HV fuse-links for transformer protection and a downstream earthing switch. Closed and opened with the push buttons on the front.

Class
E3, M1
Rated current (Ir)
200 A
Short-circuit current (Isc)
16 kA
Fuse striker
IEC 60282-1, medium
Max. fuse-link (ABB catalogue)
63 A (24 kV)
Downstream earthing switch
E2 · 5 kA / 1 s
Standards
IEC 62271-105 · IEC 62271-102
Fitted equipment
  • Horstmann WEGA 1.2 C · capacitive voltage detection, IEC 61243-5
Condition

Condition and terms

  • Used switchgear, built in 2019.
  • Dismantled in working order.
  • Sold without warranty.
  • Price on request.
  • SF₆ pressure gauge in the green zone when photographed.
  • Contains 3.1 kg of SF₆. Under the EU F-gas Regulation, installation and work on the gas system require certified personnel.
Protrafo sales specialist

Start your project

Ready to take your energy infrastructure to the next level?

Get an indicative budget price in three fields, or a full formal quote — valid for 30 days. We typically respond within one business day.

ISO 9001 IEC 60076 VCA Certified